Size for the valve.
Check the whole stroke.
A practical torque-sizing workflow: valve load, margin, operating function, available pressure and installation conditions.
Start with the valve, not the actuator model
Obtain the valve manufacturer’s torque requirement for the actual service. Valve size alone is not a torque specification. The requirement may change with valve design, seats, differential pressure and operating conditions.
Establish the required torque and margin
Identify breakaway, running and seating requirements where available. Confirm whether the supplied valve torque already contains a sizing margin before adding another one. The required safety factor depends on the project and operating duty. A common rule of thumb is 15% for on/off service, with a higher allowance for modulating or throttling duty; this is not a substitute for the application’s specified factor.
For an explicitly stated percentage margin, required sizing torque is valve torque multiplied by one plus that percentage. For example, 350 in-lb with a specified 20% margin becomes 420 in-lb. The actuator selection must also satisfy the required function, available pressure and operating temperature.
Select the function before selecting the torque chart
Use the double-acting table for normal double-acting output and the fail-safe table for Easytork stored-air fail-safe output. Fail-safe ratings represent the end of the fail stroke. Check both normal operation and the failure duty that the assembly must perform.
Check the complete travel
The actuator must provide the required torque, including the selected margin, at every relevant point of travel. A satisfactory mid-stroke value cannot compensate for insufficient breakaway or seating torque. Compare like units and like operating conditions.
For a spring-return comparison, verify the manufacturer’s spring configuration for the selected supply pressure and review powered and spring-return values. Do not substitute spring-start torque for the end-of-stroke fail requirement.
Use detailed valve torque data when available
The default method uses the valve manufacturer’s maximum required torque, including the appropriate safety factor. When the manufacturer publishes point-specific values, check those requirements individually rather than treating one peak value as the entire valve torque curve.
- BTO / ETO: break to open from the closed seat / end to open at the fully open position.
- BTC / ETC: break to close from the open seat / end to close at the fully closed position.
- RTO / RTC: running torque while opening / closing. Use direction-specific values where supplied rather than assuming one RT value represents both.
For double-acting service, check opening and closing against the available double-acting torque. For Easytork stored-air reservoir fail-close service, check normal opening against double-acting output and failure-driven closing against the fail-stroke output. For Easytork stored-air reservoir fail-open service, reverse those roles. Use the valve manufacturer’s stated travel positions for running torque; available stored-air torque changes through the fail stroke. This normal-double-acting versus stored-air-fail comparison does not apply to spring-return actuators; use their powered and spring-return torque curves.
Respect the valve’s maximum allowable shaft torque
MAST is the maximum torque the valve shaft and internal components are designed to transmit. Sufficient operating torque is only one side of selection: the actuator must also remain within the valve manufacturer’s MAST at every point in travel. A larger actuator or higher supply pressure is not automatically acceptable.
Where actuator output would exceed MAST, review a suitable regulated-pressure arrangement and recheck both normal and fail duties at the revised pressure. The selected operating pressure must satisfy both the required valve torque and the shaft-torque limit.
Use the pressure available at the actuator
Base the selection on the specified minimum available operating pressure, accounting for the actual supply arrangement.
Read the current model data
Torque is necessary, but it is not the complete selection
Confirm the actuator’s material and temperature limits against the installed environment, including heat reaching it from the process valve. Also check the mounting face, flange, drive fit and stem height. A torque match does not establish mechanical fit.
Send a concise sizing brief
- Valve manufacturer, model, size, torque data and published MAST.
- Service conditions and specified sizing margin.
- Minimum available air pressure and required operating function.
- Required fail position and the event that initiates it.
- Ambient/process temperature and relevant environmental conditions.
- Valve mounting drawing and required stroke time or positioning duty.
Check the valve-to-actuator interface → · Open Actuator Selection →
Technical references
Work through your application
Send the valve torque data and operating conditions. We can review the sizing basis and physical interface together.
Contact us →