Move less air. Get faster travel.

Easytork’s low displaced air volume helps deliver fast travel. To turn a pneumatic actuator, air must enter the driving chamber while air leaves the opposite chamber. The volume to be moved and the flow available through the complete supply and exhaust paths both influence stroke time. A large supply connection alone cannot remove a restriction elsewhere in the circuit.

Why vane geometry matters

Easytork’s vane produces rotary motion directly. Its effective leverage helps produce torque in a compact actuator. When a smaller actuator can satisfy the same valve torque requirement, less chamber volume may need to be filled and exhausted. That creates an opportunity for fast travel, provided the controls and piping can deliver the necessary flow.

Explore vane actuator principles and effective leverage arm →

Provide enough torque throughout the stroke

The actuator must provide sufficient torque at every point in the valve’s travel, including the middle of the stroke. High torque at the start or end does not compensate for insufficient torque in between. Compare available actuator torque with the valve’s full-stroke requirement and required margin.

Why the fail-safe air reservoir matters

Easytork stores the energy for the fail stroke as compressed air rather than in actuator-return springs. During normal supplied-air operation, the actuator does not have to compress an opposing return spring. This leaves more of the actuator’s torque available to operate the valve.

A typical spring-return sizing comparison uses spring-end torque of about 35% of the same actuator’s double-acting torque. Easytork’s reservoir comparison retains about 65% at fail-end. These percentages compare usable end-of-stroke torque with double-acting output.

Retaining more fail-end torque can allow a smaller actuator to meet the same valve torque requirement. A smaller chamber needs less air to fill and exhaust, which can shorten travel time when the control valve and piping provide the required airflow. Selection still uses the chosen model’s published torque throughout the required stroke.

See stored-air operation and the fail-safe torque curve →

Stroke time (seconds per direction)

Actuator modelStandard portsStandard product · Standard lead timeStandard ports + QEVSimple add-on · Minimal added cost · Standard lead timeFactory custom ports + QEVCustom modification · Custom pricing · Longer lead timeRepresentative resilient-seated butterfly valve size
EVA04110.24–0.27Not publishedNot publishedDouble-acting: 3–4″ Fail-safe: 2–3″
EVA05140.36–0.390.10–0.15Not publishedDouble-acting: 4–6″ Fail-safe: 3–4″
EVA07170.45–0.470.20–0.25Not publishedDouble-acting: 6–8″ Fail-safe: 5–6″
EVA10220.59–0.600.48Not publishedDouble-acting: 8–12″ Fail-safe: 6–10″
EVA12270.75–0.840.5–0.7Not publishedDouble-acting: 12–16″ Fail-safe: 10–12″
EVA14361.34–1.470.650.54–0.57Double-acting: 16–20″ Fail-safe: 12–18″
EVA16463.30–3.411.100.70Double-acting: 22–26″ Fail-safe: 18–22″

Notes

Testing: Cv 1.8, standard for Easytork solenoid and pilot valves; on/off operation, no load, at 80 psi air supply.

Representative resilient-seated sizing: 100 psi valve differential and 60–100 psi actuator air supply.

Fast-actuation demonstration