Normal operation.
Defined fail action.
Double-acting, fail-open and fail-close describe different requirements. Start with what the valve must do when the air supply is available, and when it is lost.
Double-acting: air powers both directions
A double-acting actuator uses the main pneumatic supply to turn in both directions. The control valve applies pressure to one actuator chamber while allowing air to leave the other. Reversing these connections reverses the rotation.
A double-acting arrangement without backup energy has no independent energy source to complete a required stroke after supply loss.
What does “inert on air loss” mean?
It means the actuator no longer has its normal pneumatic driving energy. It does not establish a guaranteed locked or fail-in-place position. The actual valve response depends on the complete assembly and control arrangement, including retained or vented air.
If the application requires a defined response to air loss, specify that response explicitly rather than assuming an ordinary double-acting assembly will provide it.
Fail-safe: retain energy for the required stroke
A fail-safe arrangement retains a secondary energy source that can drive the actuator to a specified position when the main air supply is lost. That energy may be stored pneumatically in an air reservoir or mechanically in a spring-return mechanism.
Easytork brings the actuator, standardized air reservoir and matched control accessories together as a coordinated reservoir fail-safe arrangement. Stored compressed air supplies the fail-stroke energy. The control accessory retains the reservoir air and routes it to the actuator for the configured fail stroke. Normal operation and the fail event therefore use different available air paths, even though they act on the same valve assembly.
How stored air changes the function
- Normal supply available: the actuator operates under its normal control command and the reservoir is charged.
- Supply lost: check-valve action retains the stored reservoir air.
- Fail stroke: the configured control arrangement directs that stored air to drive the valve toward its required fail position.
The actuator’s mechanical ability to rotate in both directions and the assembly’s fail-safe function are not opposing ideas. A double-acting actuator architecture can provide fail-safe service when combined with the appropriate stored-energy and control arrangement.
Fail-open and fail-close refer to the process valve
Fail-open means the assembly drives the process valve to its open position after the specified failure. Fail-close means it drives the valve to its closed position. The process requirement determines which action is appropriate; neither is automatically the right choice for every application.
Connect valve position to actuator rotation
Using the conventional quarter-turn reference, closed is 0° and open is 90°. But clockwise and counter-clockwise are rotation directions, not universal substitutes for “closed” and “open.” The valve orientation, valve design, and actuator installation establish the relationship.
For Easytork fail-safe arrangements, the installation orientation of the ESV, EPV or NTV determines the actuator’s clockwise or counter-clockwise fail action. Fail-open and fail-close are intuitive ways to describe clockwise or counter-clockwise fail action in terms of the valve’s resulting position. Which direction means open or closed depends on the valve manufacturer and installed arrangement. Confirm the resulting process-valve position and the failure event being discussed, including loss of air supply or electrical power, against the selected arrangement’s mounting and piping instructions.
Choose the control method separately
On/off versus modulating describes normal operation. Double-acting versus fail-safe describes the configured response to loss of the primary pneumatic supply. Specifying one does not answer the other.
Match the Easytork arrangement to the duty
- On/off, double-acting: a standard 5/2 solenoid arrangement supplies and exhausts the two actuator chambers. The ESV also supports the appropriate double-acting configuration.
- On/off, reservoir fail-safe: use the configured ESV arrangement, or an EPV with an external non-NAMUR-mount 3/2 solenoid providing the pilot signal.
- Modulating, double-acting: use a double-acting positioner for normal travel control.
- Modulating, reservoir fail-safe: combine the double-acting positioner with the NTV. The positioner handles normal positioning; the NTV provides the fail-safe air path.
Air-supply loss, electrical-power loss and command-signal loss are separate events. Specify the required valve response to each relevant event so the controls can be configured accordingly.
A common platform for operating functions
A common actuator platform can serve double-acting, fail-open and fail-close duties when paired with the appropriate reservoir and control configuration. This reduces the need to stock separate actuator-return spring sets for different fail-safe configurations.
Model size still follows the required normal and fail-stroke torque at the available pressure. The complete package must include the reservoir, control accessory and mounting arrangement required for its intended function.
Technical references
Contact us about the handbook →
Easytork catalogue, printed page 11 shows double-acting, fail-open and fail-close arrangements. For the individual air paths, see reservoir fail-safe controls.
Tell us the function you need
Describe the normal control duty and the valve position required on loss of air, power or command. We can work through the Easytork arrangement with you.
Contact us →